BATH/CLOSET ADDITION — HVAC Mechanical Design with ACCA Manual J, Manual S, and Manual D Reports.
During a 139-square-foot bathroom and closet addition, we redesigned the HVAC mechanical for the adjacent sleeping space that was constantly uncomfortable after a previous addition project. The Mitsubishi 1.0-ton ducted mini-split heat pump system we specified fits the small space with low cooling and heating loads perfectly.
Client: Canyon-Haus Design
Category: HVAC Mechanical Design
Date: November 2024
ACCA Manual J Heat Gain/Loss Summary
– Cooling Gain (Sensible): 8,919 BTUH
– Cooling Gain (Total): 8,919 BTUH
– Heating Loss: 8,685 BTUH
HVAC Mechanical Design Parameters
– Jurisdiction: Pima County, Arizona
– Outdoor Design Clg/Htg: 105°F/35°F
– Indoor Design Clg/Htg: 75°F/72°F
Cooling Equipment Summary
– Mitsubishi ducted split heat pump system
– Total Capacity: 1.0 ton / 371 sqft per ton
Heating Equipment Summary
– Mitsubishi ducted split heat pump system
– 3.0 kW auxiliary electric heat strip